Title: C4 SCADA Security Advisory – Rockwell Automation (Allen Bradley) Multiple
Vulnerabilities in Micrologix 1100 & 1400 Series Controllers
Date: January 15 2010
Author: Eyal Udassin (eyal udassin c4-security com)
Background
-----------------
Vendor product information, from www.ab.com :
With online editing and a built-in 10/100 Mbps EtherNet/IP port for peer-topeer
messaging, the MicroLogix 1100 controller adds greater connectivity and
application coverage to the MicroLogix family of Allen-Bradley controllers.
This next generation controller's built-in LCD screen displays controller status,
I/O status, and simple operator messages; enables bit and integer
manipulation; offers digital trim pot functionality, and a means to make
operating mode changes (Prog / Remote / Run).
With 10 digital inputs, 2 analog inputs and 6 digital outputs, the MicroLogix
1100 can handle a wide variety of tasks. The MicroLogix 1100 controllers also
support expansion I/O. Up to four 1762 I/O modules (also used on the
MicroLogix 1200 and 1400) may be added to the embedded I/O, providing
application flexibility and support of up to 80 digital I/O.
Description
----------------
Due to the sensitivity of SCADA-related vulnerabilities, we can only publicly
disclose that the Micrologix 1100 and 1400 controllers suffer from multiple
vulnerabilities that allow unauthorized control of the PLC.
Details of these vulnerabilities will be disclosed only to legitimate parties such
as asset owners (utilities), after receiving the approval of the local CERT or
any other local official entity.
Impact
----------
An attacker can exploit these vulnerabilities in order to:
Halt the system's operation (Denial of Service)
Gain unauthorized access with high privileges to the system
Leverage these vulnerabilities to attempt to find additional
vulnerabilities in the server to carry out the "field to field" attack vectors
mentioned in C4's S4 2008 paper "Control System Attack Vectors and
Examples: Field Site and Corporate Network" (http://www.c4-
security.com/index-5.html).
Affected Versions
-------------------------
AB Micrologix 1100
AB Micrologix 1400
Workaround/Fix
-----------------------
Consult with Rockwell Automation or a SCADA security company on how to
mitigate the found vulnerabilities by restricting access to the control network.
Additional Information
-------------------------------
For additional information please contact us at info_at_c4-security.com.
Note that we will respond only to verified utility personnel and governmental
agencies. Details of this vulnerability will be disclosed only to legitimate
parties such as asset owners (utilities), after receiving the approval of the
local CERT or any other local official entity.
The CVE identifier assigned to this vulnerability by CERT is CVE-2009-3739
Credit
--------
These vulnerabilities were discovered and exploited by Eyal Udassin from C4 Security (http://www.c4-security.com).
We would like to thank Rockwell Automation and CERT for their professional
handling of the vulnerability disclosure process.